Description
SIMATIC S7-1500, digital output module, DQ 64xDC 24V/0.3A SNK BA, 64 channels in groups of 16, 2 A per group at 60 °C, sourcing output, 35 mm wide cables and terminal blocks to be ordered separately as accessories
General information
Product type designation DQ 64x24VDC/0.3A SNK BA
HW functional status from FS01
Firmware version V1.0.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Prioritized startup No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V16 with HSP 0319 / V17
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V2.35 / -
Operating mode
● DQ Yes
● DQ with energy-saving function No
● PWM No
● Cam control (switching at comparison values) No
● Oversampling No
● MSO Yes
● Integrated operating cycle counter No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes; Through internal protection with 4 A per group
external protection for power supply lines (recommendation) 24 V DC/6 A miniature circuit breaker with type B tripping characteristic
Input current
Current consumption, max. 90 mA; without load
Output voltage
Rated value (DC) 24 V
Power
Power consumption from the backplane bus 0.6 W
Power loss
Power loss, typ. 4.7 W
Digital outputs
Type of digital output Transistor
Number of digital outputs 64
Current-sinking Yes
Current-sourcing No
Digital outputs, parameterizable No
Short-circuit protection No; external fusing necessary, max. 4 A per group, tripping characteristic type B or C
Limitation of inductive shutdown voltage to L+ (-53 V)
Controlling a digital input Yes
Switching capacity of the outputs
● with resistive load, max. 0.3 A
● on lamp load, max. 5 W
Load resistance range
● lower limit 80 Ω
● upper limit 10 kΩ
Output voltage
● for signal “1”, min. M+ (0.5 V)
Output current
● for signal “1” rated value 0.3 A
● for signal “1” permissible range, max. 0.3 A
● for signal “0” residual current, max. 0.5 mA
Output delay with resistive load
● “0” to “1”, max. 100 µs
● “1” to “0”, max. 500 µs
Parallel switching of two outputs
● for logic links Yes
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.5 Hz; According to IEC 60947-5-1, DC-13
● on lamp load, max. 10 Hz
Total current of the outputs
● Current per channel, max. 0.3 A
● Current per group, max. 2 A
● Current per module, max. 8 A
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Interrupts/diagnostics/status information
Diagnostics function No
Substitute values connectable No
Alarms
● Diagnostic alarm No
● Maintenance interrupt No
Diagnoses
● Monitoring the supply voltage No
● Wire break No
● short-circuit No
● Group error No
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● MAINT LED No
● Monitoring of the supply voltage (PWR-LED) Yes; via SIMATIC TOP connect connection module
● Channel status display Yes; via SIMATIC TOP connect connection module
● for channel diagnostics No
● for module diagnostics No
Potential separation
Potential separation channels
● between the channels No
● between the channels, in groups of 16; 32 when using SIMATIC TOP connect connection module
● between the channels and backplane bus Yes
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Siemens Eco Profile (SEP) Siemens EcoTech
Suitable for safety functions No
Suitable for safety-related tripping of standard modules No
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 43.8 kg
— global warming potential, (during production) [CO2 eq] 9.5 kg
— global warming potential, (during operation) [CO2 eq] 34.5 kg
— global warming potential, (after end of life cycle) [CO2 eq]