S7-1500 by siemens

S7-1500, DQ 8x230VAC/5A ST (Relay)-6ES7522-5HF00-0AB0

INR 1
Learn more
In stock

Description

SIMATIC S7-1500, digital output module DQ 8xAC 230V/5A ST; relay; 8 channels in groups of 1; 5 A per group; diagnostics; substitute value: switching cycle counter for integrated relay, the module supports the safety-oriented shutdown of load groups up to SIL1 according to EN IEC 62061:2021 and Category 2 / PL c according to EN ISO 13849-1:2015. front connector (screw terminals or push-in) to be ordered separately

General information

Product type designation DQ 8x230 V AC/5 A ST (relay)

HW functional status From FS02

Firmware version V2.1.0

● FW update possible Yes

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode No

● Prioritized startup Yes

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V12 / V12

● STEP 7 configurable/integrated from version V5.5 SP3 / -

● PROFIBUS from GSD version/GSD revision V1.0 / V5.1

● PROFINET from GSD version/GSD revision V2.3 / -

Operating mode

● DQ Yes

● DQ with energy-saving function No

● PWM No

● Cam control (switching at comparison values) No

● Oversampling No

● MSO Yes

● Integrated operating cycle counter Yes; FW V2.1.0 or higher

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes

Input current

Current consumption, max. 80 mA

Output voltage

Rated value (AC) 230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC

Power

Power consumption from the backplane bus 0.8 W

Power loss

Power loss, typ. 5 W

Address area

Address space per module

● Inputs 0 byte; typical, maximum 7 bytes, see manual for details

● Outputs 1 byte

Digital outputs

Type of digital output Relays

Number of digital outputs 8

Current-sinking Yes

Current-sourcing Yes

Digital outputs, parameterizable Yes

Short-circuit protection No

Controlling a digital input Yes; possible

Size of motor starters according to NEMA, max. 5

Digital output functions, parameterizable

● Switching tripped by comparison values No

● Freely usable digital output No

● PWM output No

● Digital output with oversampling No

Switching capacity of the outputs

● with resistive load, max. 5 A

● on lamp load, max. 1 500 W; 10 000 operating cycles

Output current

● for signal “1” rated value 5 A

● for signal “1” permissible range, min. 5 mA; 10 V

● for signal “1” permissible range, max. 8 A; thermal continuous current

● for signal “0” residual current, max. 0 A

Parallel switching of two outputs

● for logic links Yes

● for uprating No

● for redundant control of a load Yes

Switching frequency

● with resistive load, max. 2 Hz

● with inductive load, max. 0.5 Hz

● on lamp load, max. 2 Hz

Total current of the outputs

● Current per channel, max. 8 A; see additional description in the manual

● Current per group, max. 8 A; see additional description in the manual

● Current per module, max. 64 A; see additional description in the manual

Relay outputs

● Number of relay outputs 8

● Rated supply voltage of relay coil L+ (DC) 24 V

● Current consumption of relays (coil current of all relays), typ. 80 mA

● external protection for relay outputs With miniature circuit breaker with characteristic B for: cos φ 1.0: 600 A cos φ 0.5 ... 0.7: 900 A with 8 A Diazed fuse: 1 000 A

● Contact connection (internal) No

● Number of operating cycles, max. 4 000 000; see additional description in the manual

● Relay approved acc. to UL 508 Yes; 250 V AC/5 A g.p.; 120 V AC TV-4 tungsten; A300, R300

Switching capacity of contacts

— with inductive load, max. see additional description in the manual

— with resistive load, max. see additional description in the manual

Cable length

● shielded, max. 1 000 m

● unshielded, max. 600 m

Interrupts/diagnostics/status information

Diagnostics function Yes

Substitute values connectable Yes

Alarms

● Diagnostic alarm Yes

● Maintenance interrupt Yes; maintenance alarm for switching cycle counter

Diagnoses

● Monitoring the supply voltage Yes

● Wire break No

● Short-circuit No

● Group error No

Diagnostics indication LED

● RUN LED Yes; green LED

● ERROR LED Yes; red LED

● MAINT LED Yes; Yellow LED

● Monitoring of the supply voltage (PWR-LED) Yes; green LED

● Channel status display Yes; green LED

● for channel diagnostics No

● for module diagnostics Yes; red LED

Potential separation

Potential separation channels

● between the channels Yes; Switching of different phases permitted

● between the channels, in groups of 1

● between the channels and backplane bus Yes

● Between the channels and load voltage L+ Yes

Permissible potential difference

between different circuits 250 V AC between the channels and the supply voltage L+, 250 V AC between the channels and the backplane bus; 250 V AC between the channels (500 V AC when connecting different phases; basic insulation)

Isolation

Isolation tested with between the channels: 3 100 V DC; between the channels and the backplane bus: 3 100 V DC; between the channels and the supply voltage L+: 3 100 V DC; between the L+ and the backplane bus: 707 V DC (type test)

Standards, approvals, certificates

Siemens Eco Profile (SEP) Siemens EcoTech

Suitable for safety functions No

Suitable for safety-related tripping of standard modules Yes; From FS03

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 43.8 kg

— global warming potential, (during production) [CO2 eq] 9.5 kg

— global warming potential, (during operation) [CO2 eq] 34.5 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.231 kg

Highest safety class achievable for safety-related tripping of standard modules

● Performance level according to ISO 13849-1 PL c

● Category according to ISO 13849-1 Cat. 2

● SIL acc. to IEC 62061 SIL 1

● remark on safety-oriented shutdown