Description
SIMATIC S7-1500, digital output module DQ 8x230 V AC/2 A ST; TRIAC; 8 channels in groups of 1; 2 A per group; Substitute value: Front connector (screw terminals or push-in) to be ordered separately
General information
Product type designation DQ 8x230 V AC/2A ST (triac)
HW functional status from FS01
Firmware version V2.3.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Prioritized startup Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V12 / V12
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V2.3 / -
Operating mode
● DQ Yes
● DQ with energy-saving function No
● PWM No
● Cam control (switching at comparison values) No
● Oversampling No
● MSO Yes
● Integrated operating cycle counter Yes; FW V2.3.0 or higher
Output voltage
Rated value (AC) 230 V; 120/230 V AC, 50/60 Hz
Power
Power consumption from the backplane bus 0.9 W
Power loss
Power loss, typ. 10.8 W
Address area
Address space per module
● Inputs 0 byte
● Outputs 1 byte
Digital outputs
Type of digital output Triac
Number of digital outputs 8
Current-sinking No
Current-sourcing Yes
Digital outputs, parameterizable Yes
Short-circuit protection No
● built-in fuse 6.3 A melting fuse, slow-blow
Size of motor starters according to NEMA, max. 5
Digital output functions, parameterizable
● Switching tripped by comparison values No
● Freely usable digital output No
● PWM output No
● Digital output with oversampling No
Switching capacity of the outputs
● with resistive load, max. 2 A
● on lamp load, max. 50 W
Output voltage
● for signal “1”, min. L1 (-1.5 V) at maximum output current; L1 (-8.5 V) at minimum output current
Output current
● for signal “1” rated value 2 A
● for signal “1” permissible range, min. 10 mA
● for signal “1” permissible range, max. 15 A; max. 1 AC cycle
● for signal “0” residual current, max. 2 mA
Output delay with resistive load
● “0” to “1”, max. 1 AC cycle
● “1” to “0”, max. 1 AC cycle
Parallel switching of two outputs
● for logic links No
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 10 Hz
● with inductive load, max. 0.5 Hz
● on lamp load, max. 1 Hz
Total current of the outputs
● Current per channel, max. 2 A; see additional description in the manual
● Current per group, max. 2 A; see additional description in the manual
● Current per module, max. 10 A; see additional description in the manual
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Interrupts/diagnostics/status information
Diagnostics function No
Substitute values connectable Yes
Alarms
● Diagnostic alarm No
● Maintenance interrupt Yes; maintenance alarm for switching cycle counter
Diagnoses
● Monitoring the supply voltage No
● Wire break No
● short-circuit No
● Group error No
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● MAINT LED Yes; Yellow LED
● Monitoring of the supply voltage (PWR-LED) No
● Channel status display Yes; green LED
● for channel diagnostics No
● for module diagnostics Yes; red LED
Potential separation
Potential separation channels
● between the channels Yes
● between the channels, in groups of 1
● between the channels and backplane bus Yes
● Between the channels and load voltage L1 Yes
Permissible potential difference
between different circuits 250 V AC between the channels and the backplane bus; 500 V AC between the channels
Isolation
Isolation tested with 3 100 V DC
Standards, approvals, certificates
Siemens Eco Profile (SEP) Siemens EcoTech
Suitable for safety functions No
Suitable for safety-related tripping of standard modules No
Ecological footprint
● environmental product declaration Yes
Global warming potential
— global warming potential, (total) [CO2 eq] 43.8 kg
— global warming potential, (during production) [CO2 eq] 9.5 kg
— global warming potential, (during operation) [CO2 eq] 34.5 kg
— global warming potential, (after end of life cycle) [CO2 eq]