S7-1500 by siemens

S7-1500, DQ 8x24VDC/5A HS-6ES7522-5BF00-0AB0

INR 1
Learn more
In stock

Description

SIMATIC S7-1500, digital output module, DQ 8x24 V DC/5 A AUX, width 35 mm, 8 channels in groups of 4, 5 A / channel, 8 A / group, per group, two channels can be parallel-switched (2 x 8 A), 8 channels with pulse width modulation (PWM; max 12.5 kHz), front connector (screw terminal or push-in) to be ordered separately

General information

Product type designation DQ 8x24VDC/5A HS

HW functional status from FS01

Firmware version from V1.0.0

● FW update possible Yes

Product function

● I&M data Yes; I&M0 to I&M3

● Isochronous mode Yes

● Prioritized startup Yes

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V18 with HSP 0434 / V20

● STEP 7 configurable/integrated from version STEP 7 V5.7 or higher SP1 or higher

● PROFIBUS from GSD version/GSD revision revision 3 / version 5.1

● PROFINET from GSD version/GSD revision V 2.43 / -

Operating mode

● DQ Yes

● DQ with energy-saving function Yes; Valve control

● PWM Yes; max. 12.5 kHz

● Cam control (switching at comparison values) No

● Oversampling Yes

● MSO Yes

● Integrated operating cycle counter Yes

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 19.2 V

permissible range, upper limit (DC) 28.8 V

Reverse polarity protection Yes; through internal protection with 10 A per group

Input current

Current consumption, max. 40 mA; 20 mA per group, no output is activated.

Output voltage

Rated value (DC) 24 V

Power

Power consumption from the backplane bus 0.55 W

Power loss

Power loss, typ. 2.4 W

Address area

Address space per module

● Inputs 0 byte

● Outputs 1 byte

Digital outputs

Type of digital output Transistor

Number of digital outputs 8

Current-sinking No

Current-sourcing Yes; Push-pull output

Digital outputs, parameterizable Yes

Short-circuit protection Yes

● Response threshold, typ. 10 A; 4 us response time

Open-circuit detection No

Overload protection Thermal overload protection

Limitation of inductive shutdown voltage to M (-1 V)

Controlling a digital input Yes

Digital output functions, parameterizable

● Switching tripped by comparison values No

● Freely usable digital output Yes

● PWM output Yes

— Number, max. 8

— Cycle duration, parameterizable Yes; 0.08 ... 100 ms

— ON period, min. 0 %

— ON period, max. 100 %

— Resolution of the duty cycle 0.1 %

— Minimum pulse duration 30 µs

● Digital output with oversampling Yes

— Number, max. 8

— Values per cycle, max. 16

Switching capacity of the outputs

● with resistive load, max. 5 A

● with inductive load, max. 5 A

● on lamp load, max. 10 W

Load resistance range

● lower limit 4.8 Ω

● upper limit 4 kΩ

Output voltage

● for signal “1”, min. L+ (-0.8 V)

Output current

● for signal “1” rated value 5 A

● for signal “1” permissible range, max. 6 A; note derating data in the manual

● for signal “0” residual current, max. 0.5 mA

Output delay with resistive load

● “0” to “1”, typ. 3 µs

● “1” to “0”, typ. 3 µs

Parallel switching of two outputs

● for logic links No

● for uprating Yes; 8A for parallel connection of channel 0 and 1 / channel 4 and 5

● for redundant control of a load No

Switching frequency

● with resistive load, max. 12.5 kHz

● with inductive load, max. 12.5 kHz; According to IEC 60947-5-1, DC-13

● on lamp load, max. 12.5 kHz

Total current of the outputs

● Current per channel, max. 5 A; see additional description in the manual

● Current per group, max. 8 A; see additional description in the manual

● Current per module, max. 16 A; see additional description in the manual

Total current of the outputs (per module)

horizontal installation

— up to 40 °C, max. 8 A

— up to 60 °C, max. 5 A

vertical installation

— up to 40 °C, max. 5 A

Cable length

● shielded, max. 1 000 m

● unshielded, max. 600 m

Isochronous mode

Bus cycle time (TDP), min. 250 µs

Interrupts/diagnostics/status information

Diagnostics function Yes

Substitute values connectable Yes

Alarms

● Diagnostic alarm Yes

● Maintenance interrupt Yes; maintenance alarm for switching cycle counter

Diagnoses

● Monitoring the supply voltage Yes

● Wire break No

● short-circuit Yes

● Group error Yes

Diagnostics indication LED

● RUN LED Yes; green LED

● ERROR LED Yes; red LED

● MAINT LED Yes; Yellow LED

● Monitoring of the supply voltage (PWR-LED) Yes; green LED

● Channel status display Yes; green LED

● for channel diagnostics Yes; red LED

● for module diagnostics Yes; red LED

Potential separation

Potential separation channels

● between the channels No

● between the channels, in groups of 4

● between the channels and backplane bus Yes

Isolation

Isolation tested with 707 V DC (type test)

Standards, approvals, certificates

Siemens Eco Profile (SEP) Siemens EcoTech

Suitable for safety functions No

Suitable for safety-related tripping of standard modules No

Ecological footprint

● environmental product declaration Yes

Global warming potential

— global warming potential, (total) [CO2 eq] 43.8 kg

— global warming potential, (during production) [CO2 eq] 9.5 kg

— global warming potential, (during operation) [CO2 eq] 34.5 kg

— global warming potential, (after end of life cycle) [CO2 eq]