SMPS by Siemens

POWER SUPPLY-SITOP PSU6200/1AC/12VDC/2A-6EP3321-7SB00-0AX0

DATA SHEET
In stock

Description

POWER SUPPLY-SITOP PSU6200/1AC/12VDC/2A-6EP3321-7SB00-0AX0

SITOP PSU6200 12 V/2 A stabilized power supply input: 120 - 240 V AC (120 - 240 V DC) output: 12 V DC/2 A

General information

Technical Product Detail Page https://i.siemens.com/1P6EP3321-7SB00-0AX0

input

type of the power supply network 1-phase AC or DC

supply voltage at AC

● minimum rated value 120 V

● maximum rated value 240 V

● initial value 85 V

● full-scale value 264 V

supply voltage at DC 120 ... 240 V

input voltage at DC 110 ... 275 V

wide range input Yes

overvoltage overload capability 300 V AC for 30 s

buffering time for rated value of the output current in the event of power failure minimum 150 ms

operating condition of the mains buffering at Vin = 240 V

line frequency 50/60 Hz

line frequency 47 ... 63 Hz

input current

● at rated input voltage 120 V 0.45 A

● at rated input voltage 240 V 0.25 A

current limitation of inrush current at 25 °C maximum 32 A

fuse protection type 3.15 A

fuse protection type in the feeder Circuit breaker from 4 A characteristic C/6 A characteristic B to 16 A characteristic C or circuit breaker 3RV2011-1EA10 (setting 4 A) or 3RV2711-1ED10 (UL 489)

output

voltage curve at output Controlled, isolated DC voltage

number of outputs 1

output voltage at DC rated value 12 V

output voltage

● at output 1 at DC rated value 12 V

output voltage adjustable Yes; via potentiometer

adjustable output voltage 10.5 ... 12.9 V; max. 24 W

relative overall tolerance of the voltage 3 %

relative control precision of the output voltage

● on slow fluctuation of input voltage 0.3 %

● on slow fluctuation of ohm loading 0.3 %

residual ripple

● maximum 30 mV

● typical 20 mV

voltage peak

● maximum 20 mV

● typical 10 mV

display version for normal operation Green LED for 24 V OK

behavior of the output voltage when switching on Overshoot of Vout approx. 3 %

response delay maximum 1 s

voltage increase time of the output voltage

● typical 50 ms

output current

● rated value 2 A

● rated range 0 ... 2 A

supplied active power typical 24 W

short-term overload current

● on short-circuiting during the start-up typical 2 A

● at short-circuit during operation typical 2 A

bridging of equipment No