Description
POWER SUPPLY-SITOP PSU6200/1AC/12VDC/7A-6EP33237SB000AX0
SITOP PSU6200 12 V/7 A stabilized power supply input: 120 - 240 V AC (120 - 240 V DC) output: 12 V DC/ 7 A
Technical Product Detail Page https://i.siemens.com/1P6EP3323-7SB00-0AX0
input
type of the power supply network 1-phase AC or DC
supply voltage at AC
● minimum rated value 120 V
● maximum rated value 240 V
● initial value 85 V
● full-scale value 264 V
supply voltage at DC 120 ... 240 V
input voltage at DC 99 ... 275 V
wide range input Yes
overvoltage overload capability 300 V AC for 30 s
buffering time for rated value of the output current in the event of power failure minimum 90 ms
operating condition of the mains buffering at Vin = 240 V
line frequency 50/60 Hz
line frequency 47 ... 63 Hz
input current
● at rated input voltage 120 V 1.4 A
● at rated input voltage 240 V 0.8 A
current limitation of inrush current at 25 °C maximum 29 A
fuse protection type 5 A
fuse protection type in the feeder Circuit breaker 4 A characteristic C or 6 A characteristic B/C or circuit breaker 3RV2011-1EA10 (setting 4 A) or 3RV2711-1ED10 (UL 489)
output
voltage curve at output Controlled, isolated DC voltage
number of outputs 1
output voltage at DC rated value 12 V
output voltage
● at output 1 at DC rated value 12 V
output voltage adjustable Yes; via potentiometer
adjustable output voltage 12 ... 15.5 V; max. 84 W (100 W up to 45°C)
relative overall tolerance of the voltage 3 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 0.2 %
residual ripple
● maximum 30 mV
● typical 20 mV
voltage peak
● maximum 100 mV
● typical 60 mV
display version for normal operation Green LED for 24 V OK
type of signal at output Electronic contact (NO contact, contact rating 30 V DC/0.1 A) for DC O.K.
behavior of the output voltage when switching on Overshoot of Vout < 2 %
response delay maximum 0.5 s
voltage increase time of the output voltage
● typical 100 ms
output current
● rated value 7 A
● rated range 0 ... 7 A; 8.4 A up to +45°C; +60 ... +70 °C: Derating 3%/K
supplied active power typical 84 W
short-term overload current
● on short-circuiting during the start-up typical 8.4 A
● at short-circuit during operation typical 8.4 A
bridging of equipment No