Description
POWER SUPPLY-SITOP PSU6200/3AC/24VDC/10A/EX-6EP34347SC003AX0
SITOP PSU6200 Ex 24 V/10 A stabilized power supply input: 400 - 500 V AC output: 24 V DC/10 A with diagnostic interface with painted printed-circuit boards
input
type of the power supply network 3-phase AC or DC
supply voltage at AC
● minimum rated value 400 V
● maximum rated value 500 V
● initial value 323 V
● full-scale value 576 V
supply voltage at DC 500 ... 550 V
input voltage at DC 450 ... 600 V
buffering time for rated value of the output current in the event of power failure minimum 30 ms
operating condition of the mains buffering at Vin = 400 V
line frequency 50/60 Hz
line frequency 47 ... 63 Hz
input current
● at rated input voltage 400 V 0.39 A
● at rated input voltage 500 V 0.32 A
current limitation of inrush current at 25 °C maximum 13 A
fuse protection type in the feeder three-poled coupled circuit breaker from 4 A characteristic C to 16 A characteristic C or circuit breaker 3RV2011-1EA10 (setting 4 A) or 3RV2711-1ED10 (UL 489)
output
voltage curve at output Controlled, isolated DC voltage
number of outputs 1
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V
output voltage adjustable Yes; via potentiometer
adjustable output voltage 24 ... 28 V; max. 240 W (288 W up to 45°C)
relative overall tolerance of the voltage 3 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.2 %
● on slow fluctuation of ohm loading 0.1 %
residual ripple
● maximum 30 mV
● typical 20 mV
voltage peak
● maximum 30 mV
● typical 20 mV
display version for normal operation Green LED for 24 V OK
type of signal at output Electronic contact (NO contact, contact rating 30 V DC/0.1 A) for DC O.K. or diagnostic interface
behavior of the output voltage when switching on Overshoot of Vout < 2 %
response delay maximum 0.5 s
voltage increase time of the output voltage
● typical 100 ms
output current
● rated value 10 A
● rated range 0 ... 10 A; 12 A up to +45°C; +60 ... +70 °C: Derating 3%/K
supplied active power typical 240 W
short-term overload current
● on short-circuiting during the start-up typical 12 A
● at short-circuit during operation typical 12 A
parallel switching of outputs can be set with DIP switch
bridging of equipment Yes; switchable characteristic
number of parallel-switched equipment resources for increasing the power 2