SMPS by SIEMENS

POWER SUPPLY-SITOP PSU6200/3AC/24VDC/20A/EX-6EP34367SC003AX0

DATA SHEET
In stock

Description

POWER SUPPLY-SITOP PSU6200/3AC/24VDC/20A/EX-6EP34367SC003AX0

SITOP PSU6200 Ex 24 V/20 A stabilized power supply input: 400 - 500 V AC output: 24 V DC/20 A with diagnostic interface with painted printed-circuit boards

INPUT type of the power supply network 3-phase AC or DC

supply voltage at AC

● minimum rated value 400 V

● maximum rated value 500 V

● initial value 323 V

● full-scale value 576 V

supply voltage at DC 500 ... 550 V

input voltage at DC 450 ... 600 V

buffering time for rated value of the output current in the event of power failure minimum 25 ms

operating condition of the mains buffering at Vin = 400 V

line frequency 50/60 Hz

line frequency 47 ... 63 Hz

input current

● at rated input voltage 400 V 0.77 A

● at rated input voltage 500 V 0.62 A

current limitation of inrush current at 25 °C maximum 17 A

fuse protection type in the feeder three-poled coupled circuit breaker from 4 A characteristic C to 16 A characteristic C or circuit breaker 3RV2011-1EA10 (setting 4 A) or 3RV2711-1ED10 (UL 489)

output

voltage curve at output Controlled, isolated DC voltage

number of outputs 1

output voltage at DC rated value 24 V

output voltage

● at output 1 at DC rated value 24 V

output voltage adjustable Yes; via potentiometer

adjustable output voltage 24 ... 28 V; max. 480 W (576 W up to 45°C)

relative overall tolerance of the voltage 3 %

relative control precision of the output voltage

● on slow fluctuation of input voltage 0.2 %

● on slow fluctuation of ohm loading 0.1 %

residual ripple

● maximum 30 mV

● typical 20 mV

voltage peak

● maximum 30 mV

● typical 20 mV

display version for normal operation Green LED for 24 V OK

type of signal at output Electronic contact (NO contact, contact rating 30 V DC/0.1 A) for DC O.K. or diagnostic interface

behavior of the output voltage when switching on Overshoot of Vout < 2 %

response delay maximum 0.5 s

voltage increase time of the output voltage

● typical 100 ms

output current

● rated value 20 A

● rated range 0 ... 20 A; 24 A up to +45°C; +60 ... +70 °C: Derating 3%/K

supplied active power typical 480 W

short-term overload current

● on short-circuiting during the start-up typical 24 A

● at short-circuit during operation typical 24 A

parallel switching of outputs can be set with DIP switch

bridging of equipment Yes; switchable characteristic

number of parallel-switched equipment resources for increasing the power 2