POWER SUPPLY-SITOP PSU6200/1AC/24VDC/2.5A-6EP3332-7SB00-0AX0

SITOP PSU6200 24 V/2.5 A stabilized power supply input: 120 - 240 V AC (120 - 240 V DC) output: 24 V DC/2.5 A

INPUT

type of the power supply network 1-phase AC or DC

supply voltage at AC

● minimum rated value 120 V

● maximum rated value 240 V

● initial value 85 V

● full-scale value 264 V

supply voltage at DC 120 ... 240 V

input voltage at DC 110 ... 275 V

wide range input Yes

overvoltage overload capability 300 V AC for 30 s

buffering time for rated value of the output current in the event of power failure minimum 150 ms

operating condition of the mains buffering at Vin = 240 V

line frequency 50/60 Hz

line frequency 47 ... 63 Hz

input current

● at rated input voltage 120 V 1.1 A

● at rated input voltage 240 V 0.6 A

current limitation of inrush current at 25 °C maximum 32 A

fuse protection type 3.15 A

fuse protection type in the feeder Circuit breaker from 4 A characteristic C/6 A characteristic B to 16 A characteristic C or circuit breaker 3RV2011-1EA10 (setting 4 A) or 3RV2711-1ED10 (UL 489)

output

voltage curve at output Controlled, isolated DC voltage

number of outputs 1

output voltage at DC rated value 24 V

output voltage

● at output 1 at DC rated value 24 V

output voltage adjustable Yes; via potentiometer

adjustable output voltage 22.2 ... 26.4 V; max. 60 W

relative overall tolerance of the voltage 3 %

relative control precision of the output voltage

● on slow fluctuation of input voltage 0.1 %

● on slow fluctuation of ohm loading 0.1 %

residual ripple

● maximum 30 mV

● typical 20 mV

voltage peak

● maximum 30 mV

● typical 20 mV

display version for normal operation Green LED for 24 V OK

behavior of the output voltage when switching on Overshoot of Vout approx. 3 %

response delay maximum 1 s

voltage increase time of the output voltage

● typical 100 ms

output current

● rated value 2.5 A

● rated range 0 ... 2.5 A; +60 ... +70 °C: Derating 2.5%/K

supplied active power typical 60 W

short-term overload current

● on short-circuiting during the start-up typical 2.5 A

● at short-circuit during operation typical 2.5 A

bridging of equipment No