Description
POWER SUPPLY-SITOP PSU8200/1AC/24VDC/40A-6EP3337-8SB00-0AY0
SITOP PSU8200 24 V/40 A stabilized power supply input: 120/230 V AC output: 24 V DC/40 A
INPUT type of the power supply network 1-phase and 2-phase AC
supply voltage at AC Automatic selection; startup starting from Ue ≥ 90/180 V
supply voltage 120 V/230 V
input voltage 1 at AC 85 ... 132 V
input voltage 2 at AC 170 ... 264 V
wide range input No
buffering time for rated value of the output current in the event of power failure minimum 25 ms
operating condition of the mains buffering at Vin = 230 V
line frequency 50/60 Hz
line frequency 45 ... 65 Hz
input current
● at rated input voltage 120 V 15 A
● at rated input voltage 230 V 9 A
current limitation of inrush current at 25 °C maximum 50 A
I2t value maximum 8 A²·s
fuse protection type Yes
fuse protection type in the feeder Recommended miniature circuit breaker at 1-phase operation: 16 A characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2421-4BA10 (120 V) or 3RV2411-1JA10 (230 V)
output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V
output voltage adjustable Yes; via potentiometer
adjustable output voltage 24 ... 28 V; max. 960 W
relative overall tolerance of the voltage 3 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 0.1 %
residual ripple
● maximum 100 mV
● typical 50 mV
voltage peak
● maximum 240 mV
● typical 220 mV
display version for normal operation Green LED for 24 V OK; LED yellow for overload; LED red for short-circuit or latching shutdown
type of signal at output Relay contact (NO contact, rating 60 V DC/ 0.3 A) for “24 V OK”
behavior of the output voltage when switching on Overshoot of Vout approx. 3 %
response delay maximum 1.5 s
voltage increase time of the output voltage
● typical 30 ms
output current
● rated value 40 A
● rated range 0 ... 40 A; +60 ... +70 °C: Derating 3%/K
supplied active power typical 960 W
short-term overload current
● on short-circuiting during the start-up typical 120 A
● at short-circuit during operation typical 120 A
duration of overloading capability for excess current
● on short-circuiting during the start-up 25 ms
● at short-circuit during operation 25 ms
constant overload current
● on short-circuiting during the start-up typical 60 A
bridging of equipment Yes; switchable characteristic
number of parallel-switched equipment resources for increasing the power 2