Description
POWER SUPPLY-SITOP PSU8200/1ACDC/24VDC/20A-6EP1336-3BA10
SITOP PSU8200 20 A stabilized power supply input: 120-230 V AC 110-220 V DC output: 24 V DC/20 A
INPUT type of the power supply network 1-phase and 2-phase AC or DC
supply voltage at AC
● minimum rated value 120 V
● maximum rated value 230 V
● initial value 85 V
● full-scale value 275 V
supply voltage at AC temperature derating necessary at Uin<100 V AC or DC at 50 °C; additional derating at Uin<100 V: Uin=95 V Pa max=460 W, Uin=90 V Pa max=440 W, Uin=85 V Pa max=420 W
supply voltage at DC 110 ... 220 V
input voltage at DC 88 ... 350 V
wide range input Yes
buffering time for rated value of the output current in the event of power failure minimum 20 ms
operating condition of the mains buffering at Vin = 230 V
line frequency 50/60 Hz
line frequency 47 ... 63 Hz
input current
● at rated input voltage 120 V 4.6 A
● at rated input voltage 230 V 2.5 A
current limitation of inrush current at 25 °C maximum 20 A
I2t value maximum 5 A²·s
fuse protection type Yes
fuse protection type in the feeder Recommended miniature circuit breaker at 1-phase operation: 10 A characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2711-1HD10 (UL 489) at 120 V or 3RV2711-1ED10 (UL 489) at 230 V
output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V
output voltage adjustable Yes; via potentiometer
adjustable output voltage 24 ... 28 V
relative overall tolerance of the voltage 3 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 0.3 %
residual ripple
● maximum 100 mV
● typical 80 mV
voltage peak
● maximum 200 mV
● typical 100 mV
display version for normal operation Green LED for 24 V OK
type of signal at output Relay contact (NO contact, rating 60 V DC/ 0.3 A) for “24 V OK”
behavior of the output voltage when switching on No overshoot of Vout (soft start)
response delay maximum 1.5 s
voltage increase time of the output voltage
● typical 250 ms
output current
● rated value 20 A
● rated range 0 ... 20 A; +60 ... +70 °C: Derating 3%/K
supplied active power typical 480 W
short-term overload current
● at short-circuit during operation typical 60 A
duration of overloading capability for excess current
● at short-circuit during operation 25 ms
constant overload current
● on short-circuiting during the start-up typical 30 A
bridging of equipment Yes; switchable characteristic
number of parallel-switched equipment resources for increasing the power 2