SMPS by SIEMENS

POWER SUPPLY-SITOP PSU8200/3AC/24VDC/20A-6EP3436-8SB00-0AY0

DATA SHEET
In stock

Description

POWER SUPPLY-SITOP PSU8200/3AC/24VDC/20A-6EP3436-8SB00-0AY0

SITOP PSU8200 24 V/20 A stabilized power supply input: 400-500 V 3 AC output: 24 V DC/20 A

INPUT type of the power supply network 3-phase AC

supply voltage at AC

● minimum rated value 400 V

● maximum rated value 500 V

● initial value 320 V

● full-scale value 575 V

wide range input Yes

buffering time for rated value of the output current in the event of power failure minimum 15 ms

operating condition of the mains buffering at Vin = 400 V

line frequency 50/60 Hz

line frequency 47 ... 63 Hz

input current

● at rated input voltage 400 V 1.2 A

● at rated input voltage 500 V 1 A

current limitation of inrush current at 25 °C maximum 16 A

I2t value maximum 0.8 A²·s

fuse protection type none

fuse protection type in the feeder Required: 3-pole connected miniature circuit breaker 6 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489)

output

voltage curve at output Controlled, isolated DC voltage

output voltage at DC rated value 24 V

output voltage

● at output 1 at DC rated value 24 V

output voltage adjustable Yes; via potentiometer

adjustable output voltage 24 ... 28 V; max. 480 W

relative overall tolerance of the voltage 3 %

relative control precision of the output voltage

● on slow fluctuation of input voltage 0.1 %

● on slow fluctuation of ohm loading 0.2 %

residual ripple

● maximum 100 mV

voltage peak

● maximum 200 mV

display version for normal operation Green LED for 24 V OK

type of signal at output Relay contact (NO contact, rating 60 V DC/ 0.3 A) for “24 V OK”

behavior of the output voltage when switching on No overshoot of Vout (soft start)

response delay maximum 2.5 s

voltage increase time of the output voltage

● maximum 500 ms

output current

● rated value 20 A

● rated range 0 ... 20 A; +60 ... +70 °C: Derating 2%/K

supplied active power typical 480 W

short-term overload current

● at short-circuit during operation typical 60 A

duration of overloading capability for excess current

● at short-circuit during operation 25 ms

constant overload current

● on short-circuiting during the start-up typical 22 A

bridging of equipment Yes; switchable characteristic

number of parallel-switched equipment resources for increasing the power 2