SMPS by SIEMENS

POWER SUPPLY-SITOP PSU8200/3AC/24VDC/40A-6EP34378SB000AY0

DATA SHEET
In stock

Description

POWER SUPPLY-SITOP PSU8200/3AC/24VDC/40A-6EP34378SB000AY0

SITOP PSU8200 24 V/40 A stabilized power supply input: 400-500 V 3 AC output: 24 V DC/40 A

INPUT type of the power supply network 3-phase AC

supply voltage at AC

● minimum rated value 400 V

● maximum rated value 500 V

● initial value 320 V

● full-scale value 575 V

wide range input Yes

buffering time for rated value of the output current in the event of power failure minimum 10 ms

operating condition of the mains buffering at Vin = 400 V

line frequency 50/60 Hz

line frequency 45 ... 65 Hz

input current

● at rated input voltage 400 V 2.1 A

● at rated input voltage 500 V 1.7 A

current limitation of inrush current at 25 °C maximum 13 A

I2t value maximum 2.24 A²·s

fuse protection type none

fuse protection type in the feeder Required: 3-pole connected miniature circuit breaker 10 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489)

output

voltage curve at output Controlled, isolated DC voltage

output voltage at DC rated value 24 V

output voltage

● at output 1 at DC rated value 24 V

output voltage adjustable Yes; via potentiometer

adjustable output voltage 24 ... 28 V; max. 960 W

relative overall tolerance of the voltage 3 %

relative control precision of the output voltage

● on slow fluctuation of input voltage 0.1 %

● on slow fluctuation of ohm loading 0.2 %

residual ripple

● maximum 100 mV

voltage peak

● maximum 240 mV

display version for normal operation Green LED for 24 V OK

type of signal at output Relay contact (NO contact, rating 60 V DC/ 0.3 A) for “24 V OK”

behavior of the output voltage when switching on minimal overshooting (< 2 %)

response delay maximum 0.1 s

voltage increase time of the output voltage

● maximum 100 ms

output current

● rated value 40 A

● rated range 0 ... 40 A; +60 ... +70 °C: Derating 4%/K

supplied active power typical 960 W

short-term overload current

● at short-circuit during operation typical 120 A

duration of overloading capability for excess current

● at short-circuit during operation 25 ms

constant overload current

● on short-circuiting during the start-up typical 44 A

bridging of equipment Yes; switchable characteristic

number of parallel-switched equipment resources for increasing the power 2