Description
POWER SUPPLY-SITOP PSU8200/3AC/24VDC/20A-6EP3436-8SB00-0AY0
SITOP PSU8200 24 V/20 A stabilized power supply input: 400-500 V 3 AC output: 24 V DC/20 A
INPUT type of the power supply network 3-phase AC
supply voltage at AC
● minimum rated value 400 V
● maximum rated value 500 V
● initial value 320 V
● full-scale value 575 V
wide range input Yes
buffering time for rated value of the output current in the event of power failure minimum 15 ms
operating condition of the mains buffering at Vin = 400 V
line frequency 50/60 Hz
line frequency 47 ... 63 Hz
input current
● at rated input voltage 400 V 1.2 A
● at rated input voltage 500 V 1 A
current limitation of inrush current at 25 °C maximum 16 A
I2t value maximum 0.8 A²·s
fuse protection type none
fuse protection type in the feeder Required: 3-pole connected miniature circuit breaker 6 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489)
output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V
output voltage adjustable Yes; via potentiometer
adjustable output voltage 24 ... 28 V; max. 480 W
relative overall tolerance of the voltage 3 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 0.2 %
residual ripple
● maximum 100 mV
voltage peak
● maximum 200 mV
display version for normal operation Green LED for 24 V OK
type of signal at output Relay contact (NO contact, rating 60 V DC/ 0.3 A) for “24 V OK”
behavior of the output voltage when switching on No overshoot of Vout (soft start)
response delay maximum 2.5 s
voltage increase time of the output voltage
● maximum 500 ms
output current
● rated value 20 A
● rated range 0 ... 20 A; +60 ... +70 °C: Derating 2%/K
supplied active power typical 480 W
short-term overload current
● at short-circuit during operation typical 60 A
duration of overloading capability for excess current
● at short-circuit during operation 25 ms
constant overload current
● on short-circuiting during the start-up typical 22 A
bridging of equipment Yes; switchable characteristic
number of parallel-switched equipment resources for increasing the power 2