Description
SITOP SELECT/diagnosis module/4X2-10A 6EP19612BA00- SITOP select diagnostics module 4-channel input: 24 V DC/40 A output: 24 V DC/4x 10 A threshold adjustable 2-10 A
input
type of the power supply network Controlled DC voltage (SITOP select is not designed for operation with DC UPS module 40 A (6EP1 931-2FC21/-2FC42)
supply voltage at DC rated value 24 V
input voltage at DC 22 ... 30 V
overvoltage overload capability 35 V; 100 ms
input current at rated input voltage 24 V rated value 40 A
output
voltage curve at output-controlled DC voltage
formula for output voltage Vin - approx. 0.3 V
relative overall tolerance of the voltage note In accordance with the supplying input voltage
number of outputs 4
output current up to 60 °C per output rated value 10 A
adjustable current response value current of the current-dependent overload release 2 ... 10 A
type of response value setting via potentiometer
response delay maximum 5 s
product feature parallel switching of outputs No
type of outputs connection Simultaneous connection of all outputs after power up of the supply voltage, delay time of 24 ms or 100 ms programmable for sequential connection