SMPS by SIEMENS

POWER SUPPLY - SITOP SELECT/diagnosis module/4X2-10A 6EP19612BA00

Data Sheet
In stock

Description

SITOP SELECT/diagnosis module/4X2-10A 6EP19612BA00- SITOP select diagnostics module 4-channel input: 24 V DC/40 A output: 24 V DC/4x 10 A threshold adjustable 2-10 A

input

type of the power supply network Controlled DC voltage (SITOP select is not designed for operation with DC UPS module 40 A (6EP1 931-2FC21/-2FC42)

supply voltage at DC rated value 24 V

input voltage at DC 22 ... 30 V

overvoltage overload capability 35 V; 100 ms

input current at rated input voltage 24 V rated value 40 A

output

voltage curve at output-controlled DC voltage

formula for output voltage Vin - approx. 0.3 V

relative overall tolerance of the voltage note In accordance with the supplying input voltage

number of outputs 4

output current up to 60 °C per output rated value 10 A

adjustable current response value current of the current-dependent overload release 2 ... 10 A

type of response value setting via potentiometer

response delay maximum 5 s

product feature parallel switching of outputs No

type of outputs connection Simultaneous connection of all outputs after power up of the supply voltage, delay time of 24 ms or 100 ms programmable for sequential connection