Description
SIMATIC S7-1200 G2: compact CPU 1212C AC/DC/RLY; power supply: AC 85-264 V AC at 47-63 Hz; onboard I/O: 8x DI 24 V DC; 6 DO relay 2 A; memory: program 150 KB data: 500 KB, retentivity: 20 KB
Engineering with
● Programming package STEP 7 V21 or higher
Supply voltage
Rated value (AC)
● 120 V AC Yes
● 230 V AC Yes
permissible range, lower limit (AC) 85 V
permissible range, upper limit (AC) 264 V
Line frequency
● permissible range, lower limit 47 Hz
● permissible range, upper limit 63 Hz
Input current
Current consumption (rated value) 70 mA at 120 V AC; 38 mA at 240 V AC
Current consumption, max. 330 mA at 120 V AC; 200 mA at 240 V AC
Inrush current, max. 20 A; at 264 V
I²t 0.8 A²·s
Output current
for backplane bus (5 V DC), max. 1 000 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
● 24 V Yes; 20.4 to 28.8V
● Short-circuit protection Yes
● Output current, max. 300 mA
Power loss
Power loss, typ. 4 W
Storage
Work memory
● Integrated 650 kbyte
● integrated (for program) 150 kbyte
● integrated (for data) 500 kbyte
Load memory
● Integrated 8 Mbyte
● Plug-in (SIMATIC Memory Card), max. 32 Gbyte; with SIMATIC memory card
Backup
● present Yes
● maintenance-free Yes
● without battery Yes
CPU processing times
for bit operations, typ. 37 ns; / instruction
for word operations, typ. 30 ns; / instruction
for floating point arithmetic, typ. 74 ns; / instruction
CPU-blocks
Number of elements (total) 4 000; Blocks (OB, FB, FC, DB) and UDTs
OB
● Number of free cycle OBs 100
● Number of time alarm OBs 20
● Number of delay alarm OBs 20
● Number of cyclic interrupt OBs 20; with minimum OB 3x cycle of 1 ms
● Number of process alarm OBs 50
● Number of DPV1 alarm OBs 3
● Number of isochronous mode OBs 1
● Number of startup OBs 100
● Number of asynchronous error OBs 4
● Number of synchronous error OBs 2
● Number of diagnostic alarm OBs 1