Description
SIMATIC S7-1200 G2: compact CPU 1214C AC/DC/RLY; power supply: AC 85-264 V AC at 47-63 Hz; onboard I/O: 14x DI 24 V DC; 10 DO relay 2 A; memory: program 250 KB data: 750 KB, retentivity: 20 KB
General information
Product type designation CPU 1214C AC/DC/Relay
Firmware version V4.1
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode Yes; For PROFINET only
● SysLog Yes
Engineering with
● Programming package STEP 7 V21 or higher
Supply voltage
Rated value (AC)
● 120 V AC Yes
● 230 V AC Yes
permissible range, lower limit (AC) 85 V
permissible range, upper limit (AC) 264 V
Line frequency
● permissible range, lower limit 47 Hz
● permissible range, upper limit 63 Hz
Input current
Current consumption (rated value) 80 mA at 120 V AC; 44 mA at 240 V AC
Current consumption, max. 480 mA at 120 V AC; 275 mA at 240 V AC
Inrush current, max. 20 A; at 264 V
I²t 0.8 A²·s
Output current
for backplane bus (5 V DC), max. 1 600 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
● 24 V Yes; 20.4 to 28.8V
● Short-circuit protection Yes
● Output current, max. 400 mA
Power loss
Power loss, typ. 4 W
Storage
Work memory
● Integrated 1 000 kbyte
● integrated (for program) 250 kbyte
● integrated (for data) 750 kbyte
Load memory
● Integrated 8 Mbyte
● Plug-in (SIMATIC Memory Card), max. 32 Gbyte; with SIMATIC memory card
Backup
● present Yes
● maintenance-free Yes
● Without battery Yes
CPU processing times
for bit operations, typ. 37 ns; / instruction
for word operations, typ. 30 ns; / instruction
for floating point arithmetic, typ. 74 ns; / instruction
CPU-blocks
Number of elements (total) 4 000; Blocks (OB, FB, FC, DB) and UDTs
OB
● Number of free cycle OBs 100
● Number of time alarm OBs 20
● Number of delay alarm OBs 20
● Number of cyclic interrupt OBs 20; with minimum OB 3x cycle of 1 ms
● Number of process alarm OBs 50
● Number of DPV1 alarm OBs 3
● Number of isochronous mode OBs 1
● Number of startup OBs 100
● Number of asynchronous error OBs 4
● Number of synchronous error OBs 2
● Number of diagnostic alarm OBs 1
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max. 20 kbyte
Flag
● Size, max. 8 kbyte; Size of bit memory address area
Local data
● per priority class, max. 64 kbyte; max. 16 KB per block
Address area
I/O address area
● Inputs 1 kbyte; All inputs are in the process image
● Outputs 1 kbyte; All outputs are in the process image
Process image
● Inputs, adjustable 1 kbyte
● Outputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 10
● number of expansion boards (SB, CB, BB) 2
● number of signal modules (SM) 10; depends on the number of CMs
● number of communications modules (CM) 3
Time of day
Clock
● Hardware clock (real-time) Yes
● Backup time 480 h; Typical
● Deviation per day, max. 2 s; at 25 °C
Clock synchronization
● on Ethernet via NTP Yes
Digital inputs
Number of digital inputs 14; Integrated
● of which inputs usable for technological functions 8; HSC (High Speed Counting)
Sourcing/sinking input Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 14
Input voltage
● Rated value (DC) 24 V
● for signal “0” 5 V DC or 0.5 mA
● for signal “1” 15 V DC at 2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— Parameterizable 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms
— at “0” to “1”, min. 0.1 µs
— at “0” to “1”, max. 20 µs
for interrupt inputs
— parameterizable Yes
for technological functions
— parameterizable single phase: 6 HSCs @ 100 kHz & 2 standard @ 30 kHz, quadrature phase: 6 HSCs @ 80 kHz & 2 standard @ 20 kHz
Cable length
● shielded, max. 500 m; 50 m for technological functions
● unshielded, max. 300 m; for technological functions: No
Digital outputs
Number of digital outputs 10; Relays
Switching capacity of the outputs
● with resistive load, max. 2 A
● on lamp load, max. 30 W with DC, 200 W with AC
Output delay with resistive load
● “0” to “1”, max. 10 ms; max.
● “1” to “0”, max. 10 ms; max.
Switching frequency
● of the pulse outputs, with resistive load, max. Not recommended
Relay outputs
● Number of relay outputs 10
● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100 000
Cable length
● shielded, max. 500 m
● unshielded, max. 150 m
Analog inputs
Number of analog inputs 0
Analog outputs
Number of analog outputs 0
Encoder
Connectable encoders
● 2-wire sensor Yes
Interfaces
Number of PROFINET interfaces 1
1. Interface
Interface type PROFINET
Isolated Yes
automatic detection of transmission rate Yes
Autonegotiation Yes
Autocrossing Yes
Interface types
● RJ 45 (Ethernet) Yes; X1
— Transmission rate, max. 100 Mbit/s
● Number of ports 2
● integrated switch Yes