Description
SIMATIC S7-1200 G2: failsafe compact CPU 1212FC DC/DC/DC; power supply: DC 20.4-28.8 V DC; onboard I/O: 8x DI 24 V DC; 6x DO 24 V DC; memory: program 200 KB data: 500 KB, retentivity: 20 KB
General information
Product type designation CPU 1212FC DC/DC/DC
Firmware version V4.1
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode Yes; For PROFINET only
● SysLog Yes
Engineering with
● Programming package STEP 7 V21 or higher
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption (rated value) 125 mA; CPU only
Current consumption, max. 700 mA; CPU with all expansion modules
Inrush current, max. 12 A; at 28.8 V DC
I²t 0.5 A²·s
Output current
for backplane bus (5 V DC), max. 1 000 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
● 24 V Yes; L+ minus 4 V DC min.
● Short-circuit protection Yes
● Output current, max. 300 mA
Power loss
Power loss, typ. 3 W
Storage
Work memory
● integrated 700 kbyte
● integrated (for program) 200 kbyte
● integrated (for data) 500 kbyte
Load memory
● Integrated 8 Mbyte
● Plug-in (SIMATIC Memory Card), max. 32 Gbyte; with SIMATIC memory card
Backup
● present Yes
● maintenance-free Yes
● without battery Yes
CPU processing times
for bit operations, typ. 37 ns; / instruction
for word operations, typ. 30 ns; / instruction
for floating point arithmetic, typ. 74 ns; / instruction
CPU-blocks
Number of elements (total) 4 000; Blocks (OB, FB, FC, DB) and UDTs
OB
● Number of free cycle OBs 100
● Number of time alarm OBs 20
● Number of delay alarm OBs 20
● Number of cyclic interrupt OBs 20; with minimum OB 3x cycle of 1 ms
● Number of process alarm OBs 50
● Number of DPV1 alarm OBs 3
● Number of isochronous mode OBs 1
● Number of startup OBs 100
● Number of asynchronous error OBs 4
● Number of synchronous error OBs 2
● Number of diagnostic alarm OBs 1
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max. 20 kbyte
Flag
● Size, max. 8 kbyte; Size of bit memory address area
Local data
● per priority class, max. 64 kbyte; max. 16 KB per block
Address area
I/O address area
● Inputs 1 kbyte; All inputs are in the process image
● Outputs 1 kbyte; All outputs are in the process image
Process image
● Inputs, adjustable 1 kbyte
● Outputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 6
● number of expansion boards (SB, CB, BB) 1
● number of signal modules (SM) 6; depends on the number of CMs
● number of communications modules (CM) 3
Time of day
Clock
● Hardware clock (real-time) Yes
● Backup time 480 h; Typical
● Deviation per day, max. 2 s; at 25 °C
Clock synchronization
● on Ethernet via NTP Yes
Digital inputs
Number of digital inputs 8; Integrated
● of which inputs usable for technological functions 8; HSC (High Speed Counting)
Sourcing/sinking input Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 8
Input voltage
● Rated value (DC) 24 V
● for signal “0” 5 V DC or 0.5 mA
● for signal “1” 15 V DC at 2.5 mA