S7-1200 G2 by SIEMENS

CB 1241 Comm Board, RS485 - 6ES7241-1CA50-0XB0

INR 1
DATASHEET
In stock

Description

SIMATIC S7-1200 G2: CB 1241 Communication Board, interface: RS485, with push-in terminal block

General information

Product type designation CB 1241 RS 485

Input current

from backplane bus 5 V DC, typ. 75 mA

Power loss

Power loss, typ. 0.4 W

Interfaces

Interfaces/bus type RS 485

Number of interfaces 1

Point-to-point connection

● Cable length, max. 1 000 m

Integrated protocol driver

— Freeport Yes

— ASCII Yes; Available as library function

— Modbus RTU master Yes

— Modbus RTU device Yes

— USS Yes; Available as library function

Interface types

RS 485

● Transmission rate, max. 250 kbit/s

Protocols

Integrated protocols

Freeport

— Telegram length, max. 4 kbyte

— Bits per character 7 or 8

— Number of stop bits 1 (Standard), 2

— Parity no parity (standard); even, odd, mark (parity bit always 1); space (parity bit always 0)

Modbus RTU master

— Address area 1 through 65535 (Standard Modbus addressing)

— max. number of devices 247; slave numbers 1 through 247, per MODBUS network segment maximum 32 devices, additional repeaters needed to expand the network to maximum configuration

Modbus RTU device

— Address area 1 through 65535 (Standard Modbus addressing)

Interrupts/diagnostics/status information

Diagnostics function Yes

Diagnostics indication LED

● DIAG LED Yes

● for status of the outputs Yes

Degree and class of protection

IP degree of protection IP20

Standards, approvals, certificates

CE mark Yes

CSA approval No

UL approval Yes

cULus Yes

FM approval No

RCM (formerly C-TICK) Yes

KC approval Yes

Marine approval No

Ambient conditions

Free fall

● Fall height, max. 0.3 m; five times, in product package

Ambient temperature during operation

● horizontal installation, min. -20 °C

● horizontal installation, max. 60 °C; at max. voltages and max. specification

● vertical installation, min. -20 °C

● vertical installation, max. 50 °C; at max. voltages and max. specification

Ambient temperature during storage/transportation

● min. -40 °C

● max. 70 °C

Air pressure acc. to IEC 60068-2-13

● Operation, min. 540 hPa

● Operation, max. 1 140 hPa

● Storage/transport, min. 540 hPa

● Storage/transport, max. 1 140 hPa

Altitude during operation relating to sea level

● Installation altitude, min. -1 000 m

● Installation altitude, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual

Relative humidity

● Operation, max. 95 %; no condensation

Vibrations

● Vibration resistance during operation acc. to IEC 60068-2-6 3.5 mm from 5 - 8.4 Hz, 1g from 8.4 - 150 Hz

● Operation, tested according to IEC 60068-2-6 Yes

Shock testing

● tested according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Pollutant concentrations

● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free

Mechanics/material

Enclosure material (front)

● plastic Yes

Dimensions

Width 15 mm

Height 62 mm

Depth 63 mm

Weights

Weight, approx. 29 g