Description
SIMATIC S7-1200 G2: SB 1221 digital input, 8 DI 100 kHz; inputs: 8x DI 24 V DC sink/source, 100 kHz
General information
Product type designation SB 1221, DI 8x 24 V DC 100 kHz
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V20 or higher
Input current
from backplane bus 5 V DC, typ. 108 mA
Digital inputs
● from load voltage L+ (without load), max. 6 mA; per channel
Power loss
Power loss, typ. 2.4 W
Digital inputs
Number of digital inputs 8; sink / source
● in groups of 8
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 8
Input voltage
● Rated value (DC) 24 V
● for signal “0” 5 V DC or 0.5 mA
● for signal “1” 15 V DC at 2.5 mA
Input current
● for signal “0”, max. (permissible quiescent current) 0.5 mA
● for signal “1”, min. 3.3 mA
● for signal “1”, typ. 6 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable Yes; 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms
for interrupt inputs
— Parameterizable Yes
for technological functions
— Parameterizable Yes
Cable length
● shielded, max. 500 m; 500 m shielded, 50 m shielded for HSC inputs
● unshielded, max. 300 m
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm No
Diagnoses
● Monitoring the supply voltage No
Diagnostics indication LED
● DIAG LED Yes
● for status of the inputs Yes
Potential separation
Potential separation digital inputs
● between the channels No
● between the channels, in groups of 8
● Number of potential groups 1
● between the channels and backplane bus Yes; 707 V DC (type test)
Degree and class of protection
IP degree of protection IP20
Standards, approvals, certificates
Siemens Eco Profile (SEP) Siemens EcoTech
CE mark Yes
CSA approval No
UL approval Yes
cULus Yes
FM approval No
RCM (formerly C-TICK) Yes
KC approval Yes
Marine approval No
Ecological footprint
● environmental product declaration Yes; type 2 acc. to ISO 14021
Global warming potential
— global warming potential, (total) [CO2 eq] 9.53 kg
— global warming potential, (during production) [CO2 eq] 3.86 kg
— global warming potential, (during operation) [CO2 eq] 5.74 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.086 kg
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 40 °C; at max. voltages and max. specifications
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C; at rated voltages, 50 % of max. specification and alternate IO active
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C; at rated voltages, 50 % of max. specification and alternate IO active
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 540 hPa
● Operation, max. 1 140 hPa
● Storage/transport, min. 540 hPa
● Storage/transport, max. 1 140 hPa
Altitude during operation relating to sea level
● Installation altitude, min. -1 000 m
● Installation altitude, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Relative humidity
● Operation at 25 ℃ without condensation, max. 95 %
Vibrations
● Vibration resistance during operation acc. to IEC 60068-2-6 3.5 mm from 5 - 8.4 Hz, 1g from 8.4 - 150 Hz
● Operation, tested according to IEC 60068-2-6 Yes
Shock testing
● tested according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Pollutant concentrations
● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free
Mechanics/material
Enclosure material (front)
● Plastic Yes
Dimensions
Width 15 mm
Height 62 mm
Depth 63 mm
Weights
Weight, approx. 26 g