S7-1200 G2 by SIEMENS

SB 1222 Signal Board, 8DQ 24VDC 100kHz - 6ES7222-5BF50-0XB0

INR 1
DATASHEET
In stock

Description

SIMATIC S7-1200 G2: SB 1222 digital output, 8 DO 100 kHz; outputs: 8x DQ 24 V DC 0.1 A sinking/sourcing transistor, 100 kHz

General information

Product type designation SB 1222, DQ 8x 24 V DC 100 kHz

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V20 or higher

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

from backplane bus 5 V DC, typ. 30 mA

Digital outputs

● from load voltage L+, max. 15 mA

Power loss

Power loss, typ. 1 W

Digital outputs

Number of digital outputs 8

● in groups of 8

Short-circuit protection Yes

Switching capacity of the outputs

● with resistive load, max. 0.1 A

Output voltage

● Rated value (DC) 24 V

● for signal “0”, max. 1 V

● for signal “1”, min. L+ (-1.5 V)

Output current

● for signal “1” rated value 0.1 A

Output delay with resistive load

● “0” to “1”, max. 1.8 µs

● “1” to “0”, max. 1.8 µs

Total current of the outputs (per group)

horizontal installation

— up to 50 °C, max. 0.4 A

Cable length

● shielded, max. 500 m; 500 m shielded, 50 m shielded for PTO outputs

● unshielded, max. 150 m

Interrupts/diagnostics/status information

Diagnostics function Yes

Alarms

● Diagnostic alarm Yes

Diagnoses

● Monitoring the supply voltage Yes

Diagnostics indication LED

● DIAG LED Yes

● for status of the outputs Yes

Potential separation

Potential separation digital outputs

● between the channels No

● between the channels, in groups of 8

● Number of potential groups 1

● between the channels and backplane bus Yes; 707 V DC (type test)

Degree and class of protection

IP degree of protection IP20

Standards, approvals, certificates

Siemens Eco Profile (SEP) Siemens EcoTech

CE mark Yes

CSA approval No

UL approval Yes

cULus Yes

FM approval No

RCM (formerly C-TICK) Yes

KC approval Yes

Marine approval No

Ecological footprint

● environmental product declaration Yes; type 2 acc. to ISO 14021

Global warming potential

— global warming potential, (total) [CO2 eq] 9.53 kg

— global warming potential, (during production) [CO2 eq] 3.86 kg

— global warming potential, (during operation) [CO2 eq] 5.74 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.086 kg

Ambient conditions

Free fall

● Fall height, max. 0.3 m; five times, in product package

Ambient temperature during operation

● min. -20 °C

● max. 40 °C; at max. voltages and max. specifications

● horizontal installation, min. -20 °C

● horizontal installation, max. 60 °C; at rated voltages, 50 % of max. specification and alternate IO active

● vertical installation, min. -20 °C

● vertical installation, max. 50 °C; at rated voltages, 50 % of max. specification and alternate IO active

Ambient temperature during storage/transportation

● min. -40 °C

● max. 70 °C

Air pressure acc. to IEC 60068-2-13

● Operation, min. 540 hPa

● Operation, max. 1 140 hPa

● Storage/transport, min. 540 hPa

● Storage/transport, max. 1 140 hPa

Altitude during operation relating to sea level

● Installation altitude, min. -1 000 m

● Installation altitude, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual

Relative humidity

● Operation at 25 ℃ without condensation, max. 95 %

Vibrations

● Vibration resistance during operation acc. to IEC 60068-2-6 3.5 mm from 5 - 8.4 Hz, 1g from 8.4 - 150 Hz

● Operation, tested according to IEC 60068-2-6 Yes

Shock testing

● tested according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Pollutant concentrations

● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free

Mechanics/material

Enclosure material (front)

● plastic Yes

Dimensions

Width 15 mm

Height 62 mm

Depth 63 mm

Weights

Weight, approx. 29 g

Approvals / Certificates