S7-1200 G2 by SIEMENS

SB 1223 Signal Board, 4DI/4DQ 5V 200kHz - 6ES7223-7AF50-0XB0

INR 1
DATASHEET
In stock

Description

SIMATIC S7-1200 G2: SB 1223 digital I/O, 4 DI/4 DO 200 kHz; inputs: 4x DI 5 V DC, 200 kHz; outputs: 4x DQ 5 V DC 0.1 A, sinking/sourcing transistor, 200 kHz

General information

Product type designation SB 1223, DI 4x 5 V DC/DQ 4x 5 V DC 200 kHz

Engineering with

● STEP 7 TIA Portal configurable/integrated from version V20 or higher

Supply voltage

Rated value (DC) 5 V

permissible range, lower limit (DC) 4.25 V

permissible range, upper limit (DC) 6 V

Input current

from backplane bus 5 V DC, typ. 60 mA

Digital inputs

● from load voltage L+ (without load), max. 15 mA; per channel

Digital outputs

● from load voltage L+, max. 12 mA

Power loss

Power loss, typ. 1 W

Digital inputs

Number of digital inputs 4; Current-sourcing

● in groups of 4

Number of simultaneously controllable inputs

all mounting positions

— up to 40 °C, max. 4

Input voltage

● Rated value (DC) 5 V

● for signal “0” (L+ minus 1.0 V DC) ... L+ (2.2 ... 0 mA)

● for signal “1” 0 V ... (L+ minus 2.0 V DC) (20 ... 5.1 mA)

Input current

● for signal “0”, max. (permissible quiescent current) 2.2 mA

● for signal “1”, min. 5.1 mA

● for signal “1”, typ. 15 mA

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable Yes; 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms

for interrupt inputs

— parameterizable Yes

for technological functions

— parameterizable Yes

Cable length

● shielded, max. 50 m; shielded, twisted pair

Digital outputs

Number of digital outputs 4

● in groups of 4

Short-circuit protection No

Switching capacity of the outputs

● with resistive load, max. 0.1 A

Output voltage

● Rated value (DC) 5 V

● for signal “0”, max. 0.2 V

● for signal “1”, min. L+ (-0.7 V)

Output current

● for signal “1” rated value 0.1 A

● for signal “1” permissible range, max. 0.1 A

Output delay with resistive load

● “0” to “1”, max. 500 ns

● “1” to “0”, max. 500 ns

Total current of the outputs (per group)

horizontal installation

— up to 50 °C, max. 0.2 A

Cable length

● shielded, max. 50 m; twisted pair

Interrupts/diagnostics/status information

Diagnostics function Yes

Alarms

● Diagnostic alarm Yes

Diagnoses

● Monitoring the supply voltage Yes

Diagnostics indication LED

● DIAG LED Yes

● for status of the inputs Yes

● for status of the outputs Yes

Potential separation

Potential separation digital inputs

● between the channels No

● between the channels, in groups of 4

● Number of potential groups 1

● between the channels and backplane bus Yes; 707 V DC (type test)

Potential separation digital outputs

● between the channels No

● between the channels, in groups of 4

● Number of potential groups 1

● between the channels and backplane bus Yes; 707 V DC (type test)

Standards, approvals, certificates

Siemens Eco Profile (SEP) Siemens EcoTech

CE mark Yes

CSA approval No

UL approval Yes

cULus Yes

FM approval No

RCM (formerly C-TICK) Yes

KC approval Yes

Marine approval No

Ecological footprint

● environmental product declaration Yes; type 2 acc. to ISO 14021

Global warming potential

— global warming potential, (total) [CO2 eq] 9.53 kg

— global warming potential, (during production) [CO2 eq] 3.86 kg

— global warming potential, (during operation) [CO2 eq] 5.74 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.086 kg

Ambient conditions

Free fall

● Fall height, max. 0.3 m; five times, in product package

Ambient temperature during operation

● min. -20 °C

● max. 40 °C; at max. voltages and max. specifications

● horizontal installation, min. -20 °C

● horizontal installation, max. 60 °C; at rated voltages, 50 % of max. specification and alternate IO active

● vertical installation, min. -20 °C

● vertical installation, max. 50 °C; at rated voltages, 50 % of max. specification and alternate IO active

Ambient temperature during storage/transportation

● min. -40 °C

● max. 70 °C

Air pressure acc. to IEC 60068-2-13

● Operation, min. 540 hPa

● Operation, max. 1 140 hPa

● Storage/transport, min. 540 hPa

● Storage/transport, max. 1 140 hPa

Altitude during operation relating to sea level

● Installation altitude, min. -1 000 m

● Installation altitude, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual

Relative humidity

● Operation at 25 ℃ without condensation, max. 95 %

Vibrations

● Vibration resistance during operation acc. to IEC 60068-2-6 3.5 mm from 5 - 8.4 Hz, 1g from 8.4 - 150 Hz

● Operation, tested according to IEC 60068-2-6 Yes

Shock testing

● tested according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Pollutant concentrations

● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free

Mechanics/material

Enclosure material (front)

● plastic Yes

Dimensions

Width 15 mm

Height 62 mm

Depth 63 mm

Weights

Weight, approx. 28 g