SIMATIC S7-1200 G2: SB 1223 digital I/O, 4 DI/4 DO 200 kHz; inputs: 4x DI 5 V DC, 200 kHz; outputs: 4x DQ 5 V DC 0.1 A, sinking/sourcing transistor, 200 kHz
General information
Product type designation SB 1223, DI 4x 5 V DC/DQ 4x 5 V DC 200 kHz
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V20 or higher
Supply voltage
Rated value (DC) 5 V
permissible range, lower limit (DC) 4.25 V
permissible range, upper limit (DC) 6 V
Input current
from backplane bus 5 V DC, typ. 60 mA
Digital inputs
● from load voltage L+ (without load), max. 15 mA; per channel
Digital outputs
● from load voltage L+, max. 12 mA
Power loss
Power loss, typ. 1 W
Digital inputs
Number of digital inputs 4; Current-sourcing
● in groups of 4
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 4
Input voltage
● Rated value (DC) 5 V
● for signal “0” (L+ minus 1.0 V DC) ... L+ (2.2 ... 0 mA)
● for signal “1” 0 V ... (L+ minus 2.0 V DC) (20 ... 5.1 mA)
Input current
● for signal “0”, max. (permissible quiescent current) 2.2 mA
● for signal “1”, min. 5.1 mA
● for signal “1”, typ. 15 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable Yes; 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms
for interrupt inputs
— parameterizable Yes
for technological functions
— parameterizable Yes
Cable length
● shielded, max. 50 m; shielded, twisted pair
Digital outputs
Number of digital outputs 4
● in groups of 4
Short-circuit protection No
Switching capacity of the outputs
● with resistive load, max. 0.1 A
Output voltage
● Rated value (DC) 5 V
● for signal “0”, max. 0.2 V
● for signal “1”, min. L+ (-0.7 V)
Output current
● for signal “1” rated value 0.1 A
● for signal “1” permissible range, max. 0.1 A
Output delay with resistive load
● “0” to “1”, max. 500 ns
● “1” to “0”, max. 500 ns
Total current of the outputs (per group)
horizontal installation
— up to 50 °C, max. 0.2 A
Cable length
● shielded, max. 50 m; twisted pair
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
Diagnostics indication LED
● DIAG LED Yes
● for status of the inputs Yes
● for status of the outputs Yes
Potential separation
Potential separation digital inputs
● between the channels No
● between the channels, in groups of 4
● Number of potential groups 1
● between the channels and backplane bus Yes; 707 V DC (type test)
Potential separation digital outputs
● between the channels No
● between the channels, in groups of 4
● Number of potential groups 1
● between the channels and backplane bus Yes; 707 V DC (type test)
Standards, approvals, certificates
Siemens Eco Profile (SEP) Siemens EcoTech
CE mark Yes
CSA approval No
UL approval Yes
cULus Yes
FM approval No
RCM (formerly C-TICK) Yes
KC approval Yes
Marine approval No
Ecological footprint
● environmental product declaration Yes; type 2 acc. to ISO 14021
Global warming potential
— global warming potential, (total) [CO2 eq] 9.53 kg
— global warming potential, (during production) [CO2 eq] 3.86 kg
— global warming potential, (during operation) [CO2 eq] 5.74 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.086 kg
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 40 °C; at max. voltages and max. specifications
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C; at rated voltages, 50 % of max. specification and alternate IO active
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C; at rated voltages, 50 % of max. specification and alternate IO active
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 540 hPa
● Operation, max. 1 140 hPa
● Storage/transport, min. 540 hPa
● Storage/transport, max. 1 140 hPa
Altitude during operation relating to sea level
● Installation altitude, min. -1 000 m
● Installation altitude, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Relative humidity
● Operation at 25 ℃ without condensation, max. 95 %
Vibrations
● Vibration resistance during operation acc. to IEC 60068-2-6 3.5 mm from 5 - 8.4 Hz, 1g from 8.4 - 150 Hz
● Operation, tested according to IEC 60068-2-6 Yes
Shock testing
● tested according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Pollutant concentrations
● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free
Mechanics/material
Enclosure material (front)
● plastic Yes
Dimensions
Width 15 mm
Height 62 mm
Depth 63 mm
Weights
Weight, approx. 28 g