Description
SIMATIC S7-1200 G2: SM 1222 digital output, 16 DO; outputs: 16x DO, 24 V DC 0.5 A, sourcing transistor
General information
Product type designation SM 1222, DQ 16x 24 V DC/0.5 A
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 120 mA
Digital outputs
● from load voltage L+, max. 45 mA
Power loss
Power loss, typ. 3.5 W
Digital outputs
Number of digital outputs 16
● in groups of 8
Short-circuit protection No; to be provided externally
Limitation of inductive shutdown voltage to typ. (L+) -40 V, 1 W dissipation
Switching capacity of the outputs
● with resistive load, max. 0.5 A
● on lamp load, max. 5 W
Output voltage
● Rated value (DC) 24 V
● for signal “0”, max. 0.1 V; with 10 kOhm load
● for signal “1”, min. L+ (-0.5 V)
Output current
● for signal “1” rated value 0.5 A
● for signal “0” residual current, max. 10 µA
Output delay with resistive load
● “0” to “1”, max. 50 µs
● “1” to “0”, max. 200 µs
Total current of the outputs (per group)
horizontal installation
— up to 50 °C, max. 4 A; Current per mass (Group of 8)
Cable length
● shielded, max. 500 m
● unshielded, max. 150 m
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
Diagnostics indication LED
● DIAG LED Yes
● for status of the outputs Yes
Potential separation
Potential separation digital outputs
● between the channels, in groups of 8
● between the channels and backplane bus 707 V DC (type test)
Isolation
Isolation tested with 707 V DC (type test)
Degree and class of protection
IP degree of protection IP20
Standards, approvals, certificates
Siemens Eco Profile (SEP) Siemens EcoTech
CE mark Yes
CSA approval No
UL approval Yes
cULus Yes
FM approval No
RCM (formerly C-TICK) Yes
KC approval Yes
Marine approval No
Ecological footprint
● environmental product declaration Yes; type 2 acc. to ISO 14021
Global warming potential
— global warming potential, (total) [CO2 eq] 40.3 kg
— global warming potential, (during production) [CO2 eq] 7.79 kg
— global warming potential, (during operation) [CO2 eq] 32.5 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.089 kg