Description
SIMATIC S7-1200 G2: SM 1223 digital I/O, 8 DI/8 RLY; inputs: 8x DI 24 V DC sink/source; outputs: 8x DO relay 2 A
General information
Product type designation SM 1223, DI 8x 24 V DC, DQ 8x relay
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 105 mA
Digital inputs
● from load voltage L+ (without load), max. 4.1 mA; per channel
Digital outputs
● from load voltage L+, max. 9 mA; per relay coil
Power loss
Power loss, typ. 4.8 W
Digital inputs
Number of digital inputs 8
● in groups of 4
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 8
horizontal installation
— up to 40 °C, max. 8
— up to 50 °C, max. 8
vertical installation
— up to 40 °C, max. 8
Input voltage
● Rated value (DC) 24 V
● for signal “0” 5 V DC or 0.5 mA
● for signal “1” 15 V DC at 2.5 mA
Input current
● for signal “0”, max. (permissible quiescent current) 1 mA
● for signal “1”, min. 2.5 mA
● for signal “1”, typ. 4 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four
for interrupt inputs
— parameterizable No
Cable length
● shielded, max. 500 m
● unshielded, max. 300 m
Digital outputs
Number of digital outputs 8
● in groups of 8
Short-circuit protection No; to be provided externally
Switching capacity of the outputs
● with resistive load, max. 2 A
● on lamp load, max. 30 W with DC, 200 W with AC
Output voltage
● Rated value (DC) 5 V DC to 30 V DC
● Rated value (AC) 5 V AC to 250 V AC
Output current
● for signal “1” rated value 2 A
Output delay with resistive load
● “0” to “1”, max. 10 ms
● “1” to “0”, max. 10 ms
Total current of the outputs (per group)
horizontal installation
— up to 50 °C, max. 16 A; Current per mass
Relay outputs
● Number of relay outputs 8
● Rated supply voltage of relay coil L+ (DC) 24 V
● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100 000
Switching capacity of contacts
— with inductive load, max. 2 A
— on lamp load, max. 30 W with DC, 200 W with AC
— with resistive load, max. 2 A
Cable length
● shielded, max. 500 m
● unshielded, max. 150 m
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
Diagnostics indication LED
● for status of the inputs Yes
● for status of the outputs Yes
● for maintenance Yes
Potential separation
Potential separation digital inputs
● between the channels, in groups of 4
● between the channels and backplane bus Yes; 707 V DC (type test)
Potential separation digital outputs
● between the channels Relays
● between the channels, in groups of 8
● between the channels and backplane bus Yes; 4 200 V DC (type test)
Isolation
Isolation tested with 1500 V AC (type test)
Degree and class of protection
IP degree of protection IP20
Standards, approvals, certificates
Siemens Eco Profile (SEP) Siemens EcoTech
CE mark Yes
CSA approval No
UL approval Yes
cULus Yes
FM approval No
RCM (formerly C-TICK) Yes
KC approval Yes
Marine approval No
Ecological footprint
● environmental product declaration Yes; type 2 acc. to ISO 14021
Global warming potential
— global warming potential, (total) [CO2 eq] 40.3 kg
— global warming potential, (during production) [CO2 eq] 7.79 kg
— global warming potential, (during operation) [CO2 eq] 32.5 kg
— global warming potential, (after end of life cycle) [CO2 eq] -0.089 kg
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C; No condensation
● max. 40 °C; at max. voltages and max. specifications
● horizontal installation, min. -20 °C; No condensation
● horizontal installation, max. 60 °C; at rated voltages, 50 % of max. specification and alternate IO active
● vertical installation, min. -20 °C; No condensation
● vertical installation, max. 50 °C; at rated voltages, 50 % of max. specification and alternate IO active
● permissible temperature change 5°C to 55°C, 3°C / minute
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 540 hPa
● Operation, max. 1 140 hPa
● Storage/transport, min. 540 hPa
● Storage/transport, max. 1 140 hPa
Altitude during operation relating to sea level
● Installation altitude, min. -1 000 m
● Installation altitude, max. 4 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Relative humidity
● Operation at 25 ℃ without condensation, max. 95 %
Vibrations
● Vibration resistance during operation acc. to IEC 60068-2-6 3.5 mm from 5 - 8.4 Hz, 1g from 8.4 - 150 Hz
● Operation, tested according to IEC 60068-2-6 Yes
Shock testing
● tested according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Pollutant concentrations
● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free
Connection method
required front connector No
Mechanics/material
Enclosure material (front)
● Plastic Yes
Dimensions
Width 30 mm
Height 125 mm
Depth 100 mm
Weights
Weight, approx. 194 g