SIMATIC S7-1200 G2: SM 1223 digital I/O, 8 DI/8 RLY; inputs: 8x DI 24 V DC sink/source; outputs: 8x DO relay 2 A

General information

Product type designation SM 1223, DI 8x 24 V DC, DQ 8x relay

Supply voltage

Rated value (DC) 24 V

permissible range, lower limit (DC) 20.4 V

permissible range, upper limit (DC) 28.8 V

Input current

from backplane bus 5 V DC, max. 105 mA

Digital inputs

● from load voltage L+ (without load), max. 4.1 mA; per channel

Digital outputs

● from load voltage L+, max. 9 mA; per relay coil

Power loss

Power loss, typ. 4.8 W

Digital inputs

Number of digital inputs 8

● in groups of 4

Input characteristic curve in accordance with IEC 61131, type 1 Yes

Number of simultaneously controllable inputs

all mounting positions

— up to 40 °C, max. 8

horizontal installation

— up to 40 °C, max. 8

— up to 50 °C, max. 8

vertical installation

— up to 40 °C, max. 8

Input voltage

● Rated value (DC) 24 V

● for signal “0” 5 V DC or 0.5 mA

● for signal “1” 15 V DC at 2.5 mA

Input current

● for signal “0”, max. (permissible quiescent current) 1 mA

● for signal “1”, min. 2.5 mA

● for signal “1”, typ. 4 mA

Input delay (for rated value of input voltage)

for standard inputs

— parameterizable Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

for interrupt inputs

— parameterizable No

Cable length

● shielded, max. 500 m

● unshielded, max. 300 m

Digital outputs

Number of digital outputs 8

● in groups of 8

Short-circuit protection No; to be provided externally

Switching capacity of the outputs

● with resistive load, max. 2 A

● on lamp load, max. 30 W with DC, 200 W with AC

Output voltage

● Rated value (DC) 5 V DC to 30 V DC

● Rated value (AC) 5 V AC to 250 V AC

Output current

● for signal “1” rated value 2 A

Output delay with resistive load

● “0” to “1”, max. 10 ms

● “1” to “0”, max. 10 ms

Total current of the outputs (per group)

horizontal installation

— up to 50 °C, max. 16 A; Current per mass

Relay outputs

● Number of relay outputs 8

● Rated supply voltage of relay coil L+ (DC) 24 V

● Number of operating cycles, max. mechanically 10 million, at rated load voltage 100 000

Switching capacity of contacts

— with inductive load, max. 2 A

— on lamp load, max. 30 W with DC, 200 W with AC

— with resistive load, max. 2 A

Cable length

● shielded, max. 500 m

● unshielded, max. 150 m

Interrupts/diagnostics/status information

Diagnostics function Yes

Alarms

● Diagnostic alarm Yes

Diagnoses

● Monitoring the supply voltage Yes

Diagnostics indication LED

● for status of the inputs Yes

● for status of the outputs Yes

● for maintenance Yes

Potential separation

Potential separation digital inputs

● between the channels, in groups of 4

● between the channels and backplane bus Yes; 707 V DC (type test)

Potential separation digital outputs

● between the channels Relays

● between the channels, in groups of 8

● between the channels and backplane bus Yes; 4 200 V DC (type test)

Isolation

Isolation tested with 1500 V AC (type test)

Degree and class of protection

IP degree of protection IP20

Standards, approvals, certificates

Siemens Eco Profile (SEP) Siemens EcoTech

CE mark Yes

CSA approval No

UL approval Yes

cULus Yes

FM approval No

RCM (formerly C-TICK) Yes

KC approval Yes

Marine approval No

Ecological footprint

● environmental product declaration Yes; type 2 acc. to ISO 14021

Global warming potential

— global warming potential, (total) [CO2 eq] 40.3 kg

— global warming potential, (during production) [CO2 eq] 7.79 kg

— global warming potential, (during operation) [CO2 eq] 32.5 kg

— global warming potential, (after end of life cycle) [CO2 eq] -0.089 kg

Ambient conditions

Free fall

● Fall height, max. 0.3 m; five times, in product package

Ambient temperature during operation

● min. -20 °C; No condensation

● max. 40 °C; at max. voltages and max. specifications

● horizontal installation, min. -20 °C; No condensation

● horizontal installation, max. 60 °C; at rated voltages, 50 % of max. specification and alternate IO active

● vertical installation, min. -20 °C; No condensation

● vertical installation, max. 50 °C; at rated voltages, 50 % of max. specification and alternate IO active

● permissible temperature change 5°C to 55°C, 3°C / minute

Ambient temperature during storage/transportation

● min. -40 °C

● max. 70 °C

Air pressure acc. to IEC 60068-2-13

● Operation, min. 540 hPa

● Operation, max. 1 140 hPa

● Storage/transport, min. 540 hPa

● Storage/transport, max. 1 140 hPa

Altitude during operation relating to sea level

● Installation altitude, min. -1 000 m

● Installation altitude, max. 4 000 m; Restrictions for installation altitudes > 2 000 m, see manual

Relative humidity

● Operation at 25 ℃ without condensation, max. 95 %

Vibrations

● Vibration resistance during operation acc. to IEC 60068-2-6 3.5 mm from 5 - 8.4 Hz, 1g from 8.4 - 150 Hz

● Operation, tested according to IEC 60068-2-6 Yes

Shock testing

● tested according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Pollutant concentrations

● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60 % condensation-free

Connection method

required front connector No

Mechanics/material

Enclosure material (front)

● Plastic Yes

Dimensions

Width 30 mm

Height 125 mm

Depth 100 mm

Weights

Weight, approx. 194 g